Numéro de référence | DRS80US24 | ||
Description | 80-240 Watts AC-DC Converter | ||
Fabricant | XP | ||
Logo | |||
80-240 Watts
DRS80-240 Series
xppower.com
• Ultra Slim Cases
• 150% Peak Load for 4 seconds
• Wide Output Adjustment Range
• High Efficiency – Up to 92%
• 12 V, 24 V & 48 V Versions
• Low Output Ripple & Noise
• -20 ºC to 70 ºC Operating Temperature
Specification
Input
Input Voltage
• 85-264 VAC
Input Frequency
• 47-63 Hz
Input Current
• 80 W: 2 A at 85 VAC
120 W: 2 A at 85 VAC
240 W: 4 A at 85 VAC
Inrush Current
• 30 A max at 230 VAC
Power Factor
• DRS80 0.6 typical
DRS120 & 240 0.95 typical
Conforms to EN61000-3-2 Class A.
Earth Leakage Current • 1.5 mA maximum
Output
Output Voltage
• See table
Output Voltage Trim • See table
Initial Set Accuracy • ±1% at 50% load
Minimum Load
• No minimum load required
Start Up Delay
• 1 s maximum
Start Up Rise Time
• 20 ms typical
Hold Up Time
• 20 ms minimum at full load and 115 VAC
Line Regulation
• ±0.5%
Load Regulation
• ±1%
Transient Response
• 10% maximum deviation, recovering to
less than 1% within 500 µs for 50% step
load change at 0.2 A/µs
Ripple & Noise
• 100 mV pk-pk maximum, measured with
20 MHz BW
Overvoltage Protection • 12 V output: 16.5-18 V, 24 V output:
29-31.2 V, 48 V output: 57.6-62.4 V
Overload Protection
• 110-150% of rated current, constant
current limit
Short Circuit Protection • Trip and restart (hiccup mode)
Temperature
Coefficient
• ±0.02%/°C
General
Efficiency
Isolation
Switching Frequency
Signals
MTBF
• See table
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VDC Output to Ground
• DRS80 60-300 kHz variable
DRS120 & DRS240 100 kHz typical PFC
& main converter
• DRS120 & 240: DC OK Volt free contacts
• >200 kHrs to MIL HDBK217F
Environmental
Operating Temperature • -20 ºC to +70 ºC (see derating curves)
Cooling
• Natural covection
Operating Humidity • 5-95% RH, non-condensing
Storage Temperature • -25 °C to +85 °C
Shock
• IEC68-2-6, 30 g, 11ms half sine, 3 times in
each of 6 axes
Vibration
• IEC68-2-27, 10-500 Hz, 2 g 10
mins/sweep. 60 mins for each of 3 axes
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• EN55022, class B conducted & radiated
• EN61000-3-2, class A
• EN61000-3-3
• EN61000-4-2, 4 KV Contact,
8 KV Air Discharge
• EN61000-4-3, 3 V/m Perf Criteria A
• EN61000-4-4, level 2 Perf Criteria A
• EN61000-4-5, Installation Class 3
Perf Criteria B
• EN61000-4-6, 3 V Perf Criteria A
• EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms
Perf Criteria A, B, B
• UL508, EN60950, UL1604 Pending
|
|||
Pages | Pages 2 | ||
Télécharger | [ DRS80US24 ] |