DataSheetWiki


HAS50-P fiches techniques PDF

LEM - Current Transducers HAS 50~600-P

Numéro de référence HAS50-P
Description Current Transducers HAS 50~600-P
Fabricant LEM 
Logo LEM 





1 Page

No Preview Available !





HAS50-P fiche technique
Current Transducers HAS 50..600-P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50..600 A
VOUT = ±4 V
Electrical data
Primary nominal
r.m.s. current
IPN (A)
50
100
200
300
400
500
600
Primary current
measuring range
IP (A)
±150
±300
±600
±900
±900
±900
±900
Type
HAS 50-P
HAS 100-P
HAS 200-P
HAS 300-P
HAS 400-P
HAS 500-P
HAS 600-P
VC
IC
I
OC
Vd
V
b
RIS
VOUT
ROUT
R
L
Supply voltage (± 5 %)
±15
Current consumption
±15
Overload capacity
30,000
R.m.s. voltage for AC isolation test, 60 Hz, 1 mn 3
R.m.s. rated voltage, safe separation
5001)
Isolation resistance @ 500 VDC
> 1000
Output voltage @ ± IPN, RL = 10 k, TA = 25°C
±4V ±40
Output internal resistance
approx. 100
Load resistance
>1
V
mA
At
kV
V
M
mV
k
Accuracy - Dynamic performance data
X
εL
VOE
V
OH
VOT
εTC G
tr
di/dt
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity 2) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IPN0
Thermal drift of VOE HAS 50-P
HAS 100..600-P
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
di/dt accurately followed
Frequency bandwidth (small signal, -1dB) 3) 4)
< ±1
%
< ±1 % of IPN
< ±40
mV
< ±20
mV
< ±2 mV/K
< ±1 mV/K
< ±0.1 %/K
< 3 µs
> 50
A/µs
DC .. 25 kHz
General data
TA Ambient operating temperature
TS Ambient storage temperature
m Mass
Standards 5)
- 25 .. + 85 °C
- 25 .. + 85 °C
approx. 80
g
EN 50082-2
Notes : 1) Pollution class 2, overvoltage category III.
2) Linearity data exclude the electrical offset.
3) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
4) Amorphous core option for high frequency application.
5) Please consult characterisation report for more technical details and
application advice.
Features
Hall effect measuring principle
Galvanic isolation between primary
and secondary circuit
Isolation voltage 3000 V~
Low power consumption
Extended measuring range (3 x IPN)
Insulated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0
Right angle pins for direct PCB
mounting
Advantages
Easy mounting
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
Applications
AC variable speed drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
040406/0
LEM Components
www.lem.com

PagesPages 2
Télécharger [ HAS50-P ]


Fiche technique recommandé

No Description détaillée Fabricant
HAS50-P Current Transducers HAS 50~600-P LEM
LEM
HAS50-S Current Transducers HAS 50 to 600-S LEM
LEM

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche