DataSheetWiki


W67-X2Q52-20 fiches techniques PDF

Tyco - Magnetic Hydraulic Circuit Breakers

Numéro de référence W67-X2Q52-20
Description Magnetic Hydraulic Circuit Breakers
Fabricant Tyco 
Logo Tyco 





1 Page

No Preview Available !





W67-X2Q52-20 fiche technique
W6/W9 series
Magnetic Hydraulic
Circuit Breakers
Features
• Designed for the international market. UL Recognized, CSA Certified,
and VDE approved.
• Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
• Optional 10 amp auxiliary switch.
• Optional snap-in mounting. (W6)
• Several delay curve options.
• Trip-free operation.
Agency Approvals
UL: Recognized as Supplementary Protector under UL 1077. File
E69543.
CSA: Certified as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782.
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details.
Calibration: Breakers will hold 100% of rated current. Breakers may trip
between 101% and 124% of rated load (149% for 400 Hz.
units and 134% for AC/DC units). Breakers must trip at
125% of rated load and above (150% for 400 Hz. units and
135% for AC/DC units).
Dielectric Strength: 50/60 or 400 Hz., 1500V: DC, 1100V.
Insulation Resistance: 100 Megohms at 500VDC.
Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Approvals and Ratings Table 1
W6 Series
UL/CSA (All Circuit Functions)
Maximum
Voltage
65
277
277
277/480
250
250
250
Frequency
(Hz)
DC
50/60
50/60
50/60
400
400
400
Current
Phase
-
1
1
3Ø-Wye
1
1
3Ø-Wye
Interrupting
Rating
(Amps)
0.2 - 50
0.2 - 20
21 - 50
0.2 - 20
0.2 - 20
21 - 50
0.2 - 20
W9 Series
Maximum
Voltage
65
277
277/480
250
250
UL/CSA (All Circuit Functions)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
400
400
-
1
3Ø-Wye
1
3Ø-Wye
0.2 - 50
0.2 - 50
0.2 - 20
0.2 - 50
0.2 - 50
Capacity
(Amps)
2,000
5,000
2,500
5,000
2,500
1,250
2,500
Capacity
(Amps)
2,000
5,000
5,000
2,500
2,500
Approvals and Ratings Table 2
UL/CSA
Switch
Number
A
Voltage
50/60 Hz.
125
Current
(Amps)
10
Terminals
WxTxL
.093 x .020 x .250
(2.36 x .51 x 6.40)
Typical Resistance and Impedance
DC 50/60 Hz.
Current
Resistance
Impedance
(Amps)
(Ohms)
(Ohms)
0.2 90
90
1.0 1.2
1.2
2.0 0.28 0.28
5.0 0.04 0.04
10.0
0.013
0.013
20.0
0.004
0.005
30.0
0.0027
0.004
40.0
0.002
0.002
50.0
0.0015
0.0015
400 Hz.
Impedance
(Ohms)
180
2.0
0.50
0.05
0.025
0.0065
0.004
0.003
0.0025
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms).
Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm)
total excursion in 2 planes.
Fungus And Moisture Resistance: Special moisture resistant finish
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Marking: W6 units have ON and OFF molded on the rocker of rocker
actuated units (rocker actuated VDE units have international
“1” and “0”). W9 units have ON and OFF molded into the area
at the base of the toggle. International “1” and “0” symbols are
marked on the toggle for both W6 and W9.
Mounting: Panel mounted units are mounted with two #6-32 screws
from the front of the panel. Metric models for use with M3 x
0.5 screws are available. Units with snap-in mounting option
snap through the front of the panel. To maintain published
performance specifications, units should not be mounted
more than 90° from their normal upright position.
Weight: Approximately 2.5 ounces per pole.
W6 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
W9 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
VDE
Switch
Number
V1
V2
V3
Voltage
50/60 Hz.
250
250
250
Current
(Amps)
10
5
0.1
Terminals
WxTxL
.110 x .020 x .280
(2.79 x .51 x 7.11)

PagesPages 6
Télécharger [ W67-X2Q52-20 ]


Fiche technique recommandé

No Description détaillée Fabricant
W67-X2Q52-20 Magnetic Hydraulic Circuit Breakers Tyco
Tyco

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche