DataSheetWiki


FTA-60 fiches techniques PDF

COSEL - (FTA-40/-50/-60) Three phase input type

Numéro de référence FTA-60
Description (FTA-40/-50/-60) Three phase input type
Fabricant COSEL 
Logo COSEL 





1 Page

No Preview Available !





FTA-60 fiche technique
Three phase input type(1-stage filter)
FTA series(40,50,60A)
Features of FTA series
Ordering information
FTA -50
12
-683 -O
34
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
223
683
104
335
Leakage Current
(Input 250/500V 60Hz)
(335only 250/400V 60Hz)
1.0mA/2.0mA max
2.5mA/5.0mA max
3.5mA/7.0mA max
160mA/250mA max
Line to ground
capacitor
(nominal value)
22,000pF
68,000pF
100,000pF
3.3 F
*When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4Option
H:Ultra high-attenuation type
"335" is not applied.
G:With switch of line to ground capacitor
Only "335" is applied.
*Leakage current 160mA/250mA max when
the switch state is ON (switched to “ ”). 10
µA/16µA max when the switch state is OFF
(switched to “ ”).
Book type (Space-saving type)
- 1-stage filter General-purpose High-attenuation (150kHz - 1MHz)
- Selectable leakage current value, Ultra high attenuation type "335" for EU
(Wye type with neutral earth system), With switch of line to ground capacitor "-G"
Specifications
No. Items
FTA-40-683
FTA-50-683
FTA-60-683
1 Rated Voltage[V]
AC Three Phase 500 ( voltage range:528 max) *1
2 Rated Current[A]
40 50 60
3 Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity *2
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW min at room temperature and humidityhttp://www.DataSheet4U.net/ *3
5 Leakage current 250/500V 60Hz
6 DC registance
7 Safety agency approval temperatures
8 Operating temperature
2.5mA/5.0mA max
8.5mW max
6mW max
-25 to +85C (Refer to Derating Curve)
-40 to +85C (Refer to Derating Curve)
4.5mW max
9 Operating humidity
10 Storage temperature/humidity
20 to 95%RH (Non condensing)
-40 to +85C/20 to 95%RH (Non condensing)
11 Vibration
10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact
196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals
14 Case size (without projection)
UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
65X84X153 mm (WXHXD) (Option: -G refer to external view)
[2.56X3.31X6.02 inches] (WXHXD)
15 Weight
1.2kg max
*1 Only “FTA-O O-335” and “FTA-O O-335-G”,Three Phase D-connection:400 (440 max),Y-connection:500 (528 max)
*2 Only “FTA-O O-335” and “FTA-O O-335-G”, 2,800VDC (Cutoff Current = 10mA), 1minute at room temperature and humidity.
*3 Only “FTA-O O-335” and “FTA-O O-335-G”, insulation resistance specification is deleted.
Circuit Diagram
(1) Line to ground capacitor code : 223, 683, 104
LINE Case
1
2
3
CY
CY
LOAD
4
5
6
CY : Line to ground
capacitor
: Mounting Plate
(2) Line to ground capacitor code : 335
LINE Case
1
2
3
LOAD
4
5
6
CY : Line to ground
capacitor
: Mounting Plate
CY
Derating Curve
100
80
60
40
20
0
-40 -30 -20 40 50 60 70 80 90
(3) FTA-O O-335-G
LINE Case
1
2
3
Ambient Temperature [C]
LOAD
4
SW : Switch
5 (The switch
6 state is OFF)
CY : Line to ground
capacitor
: Mounting Plate
SW CY
NF-54
datasheet pdf - http://www.DataSheet4U.net/

PagesPages 2
Télécharger [ FTA-60 ]


Fiche technique recommandé

No Description détaillée Fabricant
FTA-60 (FTA-40/-50/-60) Three phase input type COSEL
COSEL
FTA-60A (FTA-40/-50/-60) Three phase input type COSEL
COSEL
FTA-6Z EMC Filters - Single-Phase Filters - FTA Small Size IEC Filter Premo
Premo

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche