DataSheetWiki


G3PC fiches techniques PDF

Omron - SSR

Numéro de référence G3PC
Description SSR
Fabricant Omron 
Logo Omron 





1 Page

No Preview Available !





G3PC fiche technique
SSR with Failure Detection Function
G3PC
Detects failures in SSRs used for heater
temperature control and simultaneously
outputs alarm signals. This product
supports the safe design of heater control
systems, and contributes to maintenance
improvements by the user.
Main detection items:
SSR short-circuits and SSR open-circuits
Alarm output possible to NPN/PNP-input devices.
The failure-detection function is built-in and power is supplied
from the main circuit power supply making wiring simple.
Slim design (width: 22.5 mm) incorporating radiator.
In addition to screw mounting, DIN track mounting is also pos-
sible.
Conforms to international standards (IEC, UL, and CSA).
Ordering Information
I List of Models
Insulation method
Phototriac coupler
Zero-cross function
Yes
Indicators
Yes
(See page 75)
I Accessories (Order Separately) www.DataSheet.co.kr
Name
Mounting Track
Dimensions
50 cm (l) × 7.3 mm (t)
1 m (l) × 7.3 mm (t)
1 m (l) × 16 mm (t)
Model number
PFP-50N
PFP-100N
PFP-100N2
Applicable output load
20 A, 100 to 240 VAC
(resistive load: AC, Class1)
Model number
G3PC-220B-VD
Specifications
I Ratings (At an Ambient Temperature of 25°C)
Detection Power Supply
Main Circuit
Rated power supply voltage
Operating voltage range
Current consumption
100 to 240 VAC (50/60 Hz)
75 to 264 VAC (50/60 Hz)
15 mA AC max. (at 200 VAC)
Operating Circuit
Input method
Rated input voltage
Operating input voltage
range
Must-operate voltage
Reset voltage
Input current
Voltage input
12 to 24 VDC
9.6 to 30 VDC
9.6 VDC max.
1 VDC min.
7 mA DC max. (at rated input voltage)
Rated load voltage
Operating voltage range
Rated carry current
Minimum load current
Inrush current resistance (peak value)
Permissible (I2t)
Applicable load
(with Class-1 AC resistive load)
100 to 240 VAC (50/60 Hz)
75 to 264 VDC (50/60 Hz)
20 A (Ta = 40)
0.1 A
220 A (60 Hz, 1 cycle)
260 A2S
4 kW (at 200 VAC)
Alarm Output
Output OFF collector voltage
Maximum carry current
Output form
30 VDC max.
0.1 A
Independent NPN open collector
SSR with Failure Detection Function G3PC
J-71
Datasheet pdf - http://www.DataSheet4U.net/

PagesPages 6
Télécharger [ G3PC ]


Fiche technique recommandé

No Description détaillée Fabricant
G3PA Extremely Thin Relays Integrated OMRON
OMRON
G3PA-VD Extremely Thin Relays Integrated OMRON
OMRON
G3PC SSR Omron
Omron
G3PC-220B-VD SSR Omron
Omron

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche