DataSheetWiki


3250-XC6DT2 fiches techniques PDF

MTU Onsite Energy - DIESEL ENGINE-GENERATOR SET

Numéro de référence 3250-XC6DT2
Description DIESEL ENGINE-GENERATOR SET
Fabricant MTU Onsite Energy 
Logo MTU Onsite Energy 





1 Page

No Preview Available !





3250-XC6DT2 fiche technique
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
3250-XC6DT2
3250 ekW / 60 Hz / Standby
2800 ekW / 60 Hz / Prime
480 - 13.8kV
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V
3
0.8
60
3250
4062.5
4887
C/F
C/F
130°C/27°C
6 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
wwwGTee.mDnepartRaatiSsoher eMeot4deUl*.c om
Connection
480V
3
0.8
60
2800
3500
4210
C/F
C/F
105°C/40°C
6 LEAD WYE
600V
3
0.8
60
3250
4062.5
3909
C/F
C/F
125°C/40°C
6 LEAD WYE
4160V
3
0.8
60
3250
4062.5
564
C/F
C/F
130°C/27°C
6 LEAD WYE
600V**
3
0.8
60
2800
3500
3368
C/F
C/F
105°C/40°C
6 LEAD WYE
4160V
3
0.8
60
2800
3500
486
C/F
C/F
105°C/40°C
6 LEAD WYE
12470V
3
0.8
60
3200
4000
185
C/F
C/F
130°C/27°C
6 LEAD WYE
13200V
3
0.8
60
3200
4000
175
C/F
C/F
130°C/27°C
6 LEAD WYE
12470V
3
0.8
60
2750
3437.5
159
C/F
C/F
105°C/40°C
6 LEAD WYE
13200V
3
0.8
60
2750
3437.5
150
C/F
C/F
105°C/40°C
6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
13800V
3
0.8
60
3200
4000
167
C/F
C/F
130°C/27°C
6 LEAD WYE
13800V
3
0.8
60
2750
3437.5
144
C/F
C/F
105°C/40°C
6 LEAD WYE

PagesPages 4
Télécharger [ 3250-XC6DT2 ]


Fiche technique recommandé

No Description détaillée Fabricant
3250-XC6DT2 DIESEL ENGINE-GENERATOR SET MTU Onsite Energy
MTU Onsite Energy

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche