DataSheet.es    


PDF E5EN Data sheet ( Hoja de datos )

Número de pieza E5EN
Descripción Temperature Controller
Fabricantes Omron 
Logotipo Omron Logotipo



Hay una vista previa y un enlace de descarga de E5EN (archivo pdf) en la parte inferior de esta página.


Total 28 Páginas

No Preview Available ! E5EN Hoja de datos, Descripción, Manual

www.DataSheet4U.com
Digital Temperature Controllers
E5EN
Compact and Intelligent Temperature
Controllers
Depth of only 78 mm.
Various temperature inputs: thermocouple, plati-
num resistance thermometer, non-contact temper-
ature sensor, and analog inputs.
Auto-tuning and self-tuning available. Auto-tuning
is possible even while self-tuning is being
executed.
Heating or heating/cooling control is available.
Event input allows multiple SP selection and
run/stop function.
Water-resistant construction (NEMA4X: equivalent
to IP66).
Conforms to UL, CSA, and IEC safety standards as
well as CE marking.
48(W) x 96(H) x 78(D) mm
Ordering Information
E5EN Standard Models
Size
Power supply
voltage
No. of alarm
points
1/8 DIN
100 to 240 VAC 3
48(W) x 96(H) x
78(D) mm
24 VAC/VDC 3
Output
Relay
Voltage output
(for driving
SSR)
Current
Relay
Voltage output
(for driving
SSR)
Current
Heater
burnout alarm
Thermocouple
model
No E5EN-R3MTC-500
Yes E5EN-R3HMTC-500
No E5EN-Q3MTC-500
Yes E5EN-Q3HMTC-500
No E5EN-C3MTC-500
No E5EN-R3MTC-500
Yes E5EN-R3HMTC-500
No E5EN-Q3MTC-500
Yes E5EN-Q3HMTC-500
No E5EN-C3MTC-500
Platinum
resistance
thermometer
model
E5EN-R3MP-500
E5EN-R3HMP-500
E5EN-Q3MP-500
E5EN-Q3HMP-500
E5EN-C3MP-500
E5EN-R3MP-500
E5EN-R3HMP-500
E5EN-Q3MP-500
E5EN-Q3HMP-500
E5EN-C3MP-500
Note: 1. A Current Transformer (CT) is not provided with the Unit. Be sure to order one when ordering the E5EN.
2. When the heating and cooling function is used, the number of alarm outputs will be reduced to 2.
3. When the heating and cooling function or the heater burnout alarm is used, one of the alarm outputs will be disabled for each func-
tion used.
4. Specify the power supply specifications when ordering.
E5EN Option Units
Current Transformer (Sold Separately)
The E5EN provides communication or event input functionality
when mounted with one of the following Option Units.
Name
Model
Function
Model
Hole diameter
E54-CT1
5.8 dia.
E54-CT3
12.0 dia.
Communication
Unit
Event Input Unit
E53-AK01
E53-AK03
E53-AKB
RS-232C communication
RS-485 communication
Event input
Terminal Cover (Sold Separately)
Model
E53-COV03
10

1 page




E5EN pdf
www.DEa5taEShNeet4U.com
Nomenclature
Operation
indicators
Temperature
unit
Operation
indicators
Mode key
Level key
No.1 display
No.2 display
Up key
Down key
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5EN
Panel Cutouts
Mounted Separately
Group Mounted
(48number of units -2.5) +1.0
0
Group mounting does
not allow waterproofing.
Recommended panel thickness is 1 to 8 mm.
Group mounting is not possible in the vertical
direction. (Maintain the specified mounting space
between Controllers when they are group
mounted.)To mount the E5EN so that it is
waterproof, apply the waterproof packing to the
E5EN.
To mount the E5EN so that it is waterproof, apply
the waterproof packing to the E5EN.
When two or more E5ENs are mounted, make
sure that the surrounding temperature does not
exceed the allowable operating temperature
specified in the specifications.
14

5 Page





E5EN arduino
www.DatEaS5hAeeNt4U/E.co5mEN/E5CN/E5GN
E5GN
Mounting
1. Insert the E5GN into the mounting hole in the panel from the
front.
2. Push the adapter along the E5GN body from the terminals up
to the panel, and secure it temporarily.
3. Tighten the two fixing screws on the adapter. When tightening
screws, tighten the two screws alternately keeping the torque
to within approximately 0.29 to 0.39 Njm.
Adapter
Waterproof packing
Panel
E5AN/E5EN/E5CN/E5GN
2. Draw out the terminal plate as it is.
3. Before you insert the terminal plate again, make sure that the
pins match the positions of the holes in the terminal plate.
Removing and Attaching the Terminal Plate
The E5GN can be replaced by removing the terminal plate.
1. Press down hard on the fasteners on both sides of the
terminals to unlock the terminal plate and pull upwards.
Wiring Precautions
E5AN/E5EN/E5CN
Separate input leads and power lines to protect the
E5AN/E5EN/E5CN and its lines from external noise.
We recommend using solderless terminals when wiring the
E5AN/E5EN/E5CN.
Tighten the terminal screws using a torque between 0.74 and
0.90 N j m.
Use the following type of solderless terminals for M3.5 screws.
7.2 mm max.
E5GN
Connect the terminals as specified below.
Terminal No.
1 to 6
7 to 9
Cables
AWG24 to AWG14
AWG28 to AWG22
Pin terminals
2.1 dia. max.
1.3 dia. max.
The exposed current-carrying part to be inserted into terminals
must be 5 to 6 mm.
7.2 mm max.
5 to 6 mm
5 to 6 mm
Electrical wire
Pin terminal
Tighten the terminal screws to the torque specified below.
Terminal No.
Screw
1 to 6
7 to 9
M2.6
M2
Maximum tightening
torque
0.23 to 0.25 N j m
0.12 to 0.14 N j m
31

11 Page







PáginasTotal 28 Páginas
PDF Descargar[ Datasheet E5EN.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
E5EJ(E5xJ) Temperature ControllerOmron
Omron
E5EJ-A2HB(E5xJ) Temperature ControllerOmron
Omron
E5EJ-xxxx(E5xJ) Temperature ControllerOmron
Omron
E5EKDigital ControllerOmron
Omron

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar