DataSheetWiki


FLEX405 fiches techniques PDF

ETC - Fire Alarm Control Panel

Numéro de référence FLEX405
Description Fire Alarm Control Panel
Fabricant ETC 
Logo ETC 





1 Page

No Preview Available !





FLEX405 fiche technique
Flex 405
Fire Alarm Control Panel with built-in DACT
and remote-site upload/download capability
Description
The Gamewell Flex 405 is a 24-volt,
five-zone Fire Alarm Control Panel
FACP) with built-in communicator
and remote-site upload/download
capability. The integral communica-
tor transmits event information
(alarms, troubles, supervisories,
faults, etc.) to a UL-Listed central
station. The Flex 405 may be used
in a variety of cost-effective applica-
tions, including: local fire alarm
control panel (communicator dis-
abled), fire alarm control panel/
communicator, stand-alone sprin-
kler supervisory communicator, or
slave communicator to a UL-Listed
host fire alarm panel (requires normally-open dry contacts to trigger five
channels). Selectable transmission formats allow the Flex 405 to communi-
cate to virtually all central stations.
www.DataSheet4U.com
Remote-Site Upload/Download
The Flex 405 may be downloaded or uploaded without affecting the system
fire protection. Download system programming, and upload key system
information such as: current system status, history and walk test files;
zone, AC line, NAC 1 and NAC 2, resettable power and battery voltages;
and system programming. Upload or download within one minute without
affecting normal fire panel functions. The upload/download function also
features multiple security techniques. The Flex 405 requires the PK-CD
programming kit, which works with most Hayes-compatible modems
(consult factory for listing).
Features
• Five programmable Initiating Device Circuits
(zones). Each zone may be programmed for:
two-wire smoke detectors, normally open
contact devices (pull stations, heat
detectors), four-wire smoke detectors,
waterflow operation, supervisory operation,
auto-reset supervisory operation.
• Two built-in, Class A or B (Style Z or Y)
Notification Appliance Circuits (NACs). NACs
may be programmed: silenceable, non-
silenceable (a strobe circuit can keep flashing
after the panel is silenced), auto-silence
(program 5 to 30 minutes), silence inhibit (60
seconds), coding (march time, temporal,
California).
• 3.0 amps of notification appliance power,
expandable to 5.0 amps (meets the critical
power requirements for ADA and UL-1971
devices).
• Two built-in Form-C Alarm and Trouble relays.
• Supervisory and communication fail outputs.
• Dual-line rotary- or Touch-Tone®-dial DACT
interfaces to public telephone network
(leased phone lines are not required).
• 24-Volt operation.
• Built-in voltmeter measures: zone voltage;
primary AC line voltage; battery voltage;
NAC(s) voltage; resettable 24-volt power.
• Surface Mount Technology (SMT).
• Fully programmable via built-in keypad (no
costly external programmers necessary).
• Complies with NFPA 72 (Local, Central
Station and Remote Station [DACT only – not
polarity reversal] Fire Alarm Systems).
• Reporting formats include:
3+1, 4+1, 4+2 Standard + Expanded;
4+1, 4+2, Ademco Express.
• Integral battery charger for up to 60 hours of
standby power.
• Fuseless, power-limited technology meets UL
power-limiting requirements.
• Programmable alarm presignal timer, alarm
verification timer, and optional trouble
reminder.
• Single-person walk test. Fire drill function.
• Zone disable capability (software).
• 32-Event history buffer with time-and-date
stamp. Accurate real-time clock/calendar.
• Extensive built-in transient protection.
• Electronics and operational controls fully
enclosed in a lockable cabinet capable of
housing up to 7 AH batteries.
Optional: contact-by-zone module, remote
annunciator, printer interface for on- or off-
line printing.
Listings
Listings and approvals below apply to the
basic Flex 405 panel. In some cases, certain
modules may not be listed by certain approval
agencies, or listing may be in process.
Consult factory for latest listing status.
• UL Listed.
• CSFM approved: file 7165-1288:179.
• MEA approved: file 366-04-E.
Flex 405 CS-2405 02/15/05
Page 1 of 4

PagesPages 4
Télécharger [ FLEX405 ]


Fiche technique recommandé

No Description détaillée Fabricant
FLEX405 Fire Alarm Control Panel ETC
ETC

US18650VTC5A

Lithium-Ion Battery

Sony
Sony
TSPC106

PCI Bus Bridge Memory Controller

ATMEL
ATMEL
TP9380

NPN SILICON RF POWER TRANSISTOR

Advanced Semiconductor
Advanced Semiconductor


www.DataSheetWiki.com    |   2020   |   Contactez-nous  |   Recherche